Wire Ampacity Chart (Copper & Aluminum)
Allowable ampacities for copper and aluminum conductors based on NEC Table 310.16 — plus the breaker pairings and small-conductor rules that decide what you can actually install.
Last updated: November 2026
Copper Wire Ampacity Chart
The three columns correspond to the temperature rating of the conductor's insulation and its terminations: 60°C covers NM-B (Romex) and UF-B cable, 75°C covers THWN/THHN conductors with standard breaker and lug terminations (the column used for most sizing), and 90°C applies only when every termination in the circuit is rated 90°C — rare in residential work, but the column used as a starting point for derating calculations.
| Copper Size (AWG) | 60°C (NM-B, UF-B) | 75°C (THWN, SE) | 90°C (THHN, XHHW-2) |
|---|---|---|---|
| 14 | 15A | 20A* | 25A* |
| 12 | 20A | 25A* | 30A* |
| 10 | 30A | 35A* | 40A* |
| 8 | 40A | 50A | 55A |
| 6 | 55A | 65A | 75A |
| 4 | 70A | 85A | 95A |
| 3 | 85A | 100A | 115A |
| 2 | 95A | 115A | 130A |
| 1 | — | 130A | 145A |
| 1/0 | — | 150A | 170A |
| 2/0 | — | 175A | 195A |
| 3/0 | — | 200A | 225A |
| 4/0 | — | 230A | 260A |
*Asterisked values are limited by the small-conductor rule below — a 14 AWG copper conductor is listed at 20A in the 75°C column, but it may never be protected by a breaker larger than 15A.
Aluminum Wire Ampacity Chart
Aluminum conductors carry less current per gauge than copper — the working rule of thumb is that aluminum needs to be about two sizes larger for the same job. In modern residential work aluminum is used almost exclusively for feeders and service conductors (6 AWG and up), where its lower cost per amp beats copper:
| Aluminum Size (AWG) | 75°C (THWN, SE, USE) | 90°C (THHN, XHHW-2) |
|---|---|---|
| 12 | 20A* | 25A* |
| 10 | 30A* | 35A* |
| 8 | 40A | 45A |
| 6 | 50A | 55A |
| 4 | 65A | 75A |
| 3 | 75A | 85A |
| 2 | 90A | 100A |
| 1 | 100A | 115A |
| 1/0 | 120A | 135A |
| 2/0 | 135A | 150A |
| 3/0 | 155A | 175A |
| 4/0 | 180A | 205A |
*Capped by the small-conductor rule: 12 AWG aluminum is limited to a 15A breaker and 10 AWG aluminum to 25A, regardless of the table values.
What Size Wire for Each Breaker?
The practical question behind every ampacity lookup. The copper NM-B column is the answer for standard Romex house wiring (which must use the 60°C rating); the THWN column applies to individual conductors in conduit with 75°C terminations:
| Breaker Size | Copper NM-B (Romex) | Copper THWN in Conduit | Aluminum (75°C) |
|---|---|---|---|
| 15A | 14 AWG | 14 AWG | — |
| 20A | 12 AWG | 12 AWG | — |
| 30A | 10 AWG | 10 AWG | 8 AWG |
| 40A | 8 AWG | 8 AWG | 8 AWG |
| 50A | 6 AWG | 8 AWG | 6 AWG |
| 60A | 6 AWG† | 6 AWG | 4 AWG |
| 100A feeder | — | 3 AWG | 1 AWG |
| 200A service | — | 3/0 AWG | 4/0 AWG‡ |
†6 AWG NM-B is rated 55A, but NEC 240.4(B) allows rounding up to the next standard breaker size (60A) when the load doesn't exceed the conductor rating. ‡For a dwelling's main service, NEC 310.12 allows conductors sized at 83% of the service rating — which is how 4/0 aluminum (180A) and 2/0 copper (175A) legally serve a 200A residential service. Longer runs often need a size up anyway for voltage drop — check with the wire size calculator, which handles both rules automatically.
The Small-Conductor Rule (NEC 240.4(D))
The ampacity tables are not the final word for small wires. NEC 240.4(D) caps the overcurrent protection for small conductors regardless of what the table columns allow: 14 AWG copper → 15A, 12 AWG copper → 20A, 10 AWG copper → 30A, 12 AWG aluminum → 15A, and 10 AWG aluminum → 25A. This is why the familiar pairings — 14 gauge on a 15 amp circuit, 12 gauge on a 20, 10 gauge on a 30 — are hard rules for branch circuits rather than conventions, even though the 75°C column appears to permit more. Our breaker size calculator applies these caps for you.
Why Ampacity Isn't the Whole Answer
Two things routinely push the right wire size above what this chart says. The first is voltage drop: on long runs, resistance eats voltage, and the NEC recommends staying under 3% on branch circuits. A 50A, 240V circuit to a detached garage 100 feet away passes the ampacity check with 8 AWG copper, but drops about 3.3% of its voltage — so the correct answer is 6 AWG. Run your distance through the voltage drop calculator to check. The second is derating: more than three current-carrying conductors bundled in one cable or conduit, or ambient temperatures above 30°C (attics in summer easily exceed this), require reducing the table values — starting from the 90°C column for THHN. Continuous loads such as EV chargers must also be wired at 125% of the load, which is why a 48A charger needs a 60A circuit and 6 AWG copper.
Citing This Data
Writers, researchers, and publishers are welcome to reference this chart. Values are based on NEC Table 310.16 (allowable ampacities, not more than three current-carrying conductors, 30°C ambient) with the NEC 240.4(D) small-conductor limits noted. Please attribute to DIYCalcTools with a link to diycalctools.com/reference/wire-ampacity-chart/ — for example: “8 AWG copper is rated for 40 amps on NM-B cable and 50 amps at 75°C (DIYCalcTools).” This page is reviewed against the current NEC edition; the date at the top reflects the last revision.